SBWW Home

Design Data

Nebraska Boiler

1.

Continuous Capacity

100,000 PPH (45,360 Kg/HR)

2.

Design Pressure

250 PSIG (1,724 KPa(g))

3.

Operating Pressure

175 PSIG (1,207 KPa(g))

4.

Feed water Temperature

227o F (108o C)

5.

Furnace Volume

1,545 CU. FT. (43 M3)

6.

Convection Heating Surface

5,820 SQ. FT. (541 M2)

7.

Radiant Heating Surface

1,092 SQ. FT. (Net EFF.) (101 M2)

8.

Radiant Heating Surface

832 SQ. FT. (ASME) (77 M2)

9.

Total Heating Surface

6,912 SQ. FT. (Net EFF.) (642 M2)

10.

Total Heating Surface

6,652 SQ. FT. (ASME) (618 M2)

11.

Boiler Weight, Dry

126,610 LBS. (57,430 Kg)

12.

Total Operating Weight

154,950 LBS. (70,286 Kg)